ISQBX
The ISQBX series control valve is an electronic pressure regulator designed to precisely and proportionally control the pressure of gases based on an electronic signal. The ISQBX is an FM approved and rated Intrinsically Safe valve designed for hazardous locations (see below for complete classification).
The FM Approved Intrinsically Safe ISQBX operates using two normally closed solenoid valves, a pressure sensor and a control circuit. One valve is actuated to allow unregulated supply media into the system. The second valve actuates to allow working media to vent to atmosphere. The pressure sensor provides feedback to the control circuit. The control circuit compares the pressure sensor feedback to the user supplied electronic command signal and actuates the appropriate valve until the two signals match.
Request Quote
%
Accuracy ±
%
Repeatability ±
Max Flow (SCFM)
Max P2 (PSIG)
ISQBX Downloads & Links
Documents | Links | Downloads |
Installation Guide | Hazardous Location Product FAQ | File Request Form |
Hazardous Location Product Brochure | ISQB-Series | Submit Form to Download ISQBX .STEP File |
ISQBX Technical Specifications
Pressure Range | Accuracy | Repeatability | Max Flow |
Vacuum thru 150 PSI (10.3 Bar) | ±0.5% F.S. | ±0.2% F.S. | 0.8 SCFM (23 LPM) |
Port Size | Durability | Operating Temps | Filtration |
1/8″ NPT | Immune to shock & vibration (up to 25 Gs) | 32-104°F (0-40°C) | 40 Micron |
Your browser does not support iframes.
Your browser does not support iframes.
ISQBX | Intrinsically Safe
The ISQBX Intrinsically Safe valve is rated by Factory Mutual (FM) and approved for specific hazardous locations including: Class I, II, III, Division 1, Groups C, D, E, F and G. The ISQBX may be used with any non-corrosive compressible media compatible with the wetted materials.
Special Condition for Use:
The apparatus enclosure contains aluminum which is considered to constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact or friction.
NOTES: End user must determine fitness and suitability of the ISQBX control valve for their application. The ISQBX requires the use of Intrinsically Safe barriers.