Solving Steam Control Issues & Offering Alternatives

Proportion-Air Case Study 

Steam Control Issues

Steam Control Issues | Losing Steam – Figuratively and Literally

Cooking on a mass scale requires no small amount of precise engineering. A corn tortilla manufacturer was having steam control issues controlling temperature with the saturated steam used to heat the cooking kettles for the corn. The manufacturer came to Proportion-Air seeking a solution.

A visit to the plant revealed the company was using a particular I to P transducer, steam valve, RTD (resistance temperature sensor), and PID (proportional-integral-derivative) loop to control the temperature. The issue arose out of a regular failure of the I to P transducer.

The I to P was replaced with a Proportion Air QB1, which is better able to withstand standard industrial air (I to Ps require instrument air, which is defined as air filtered to less than 5 microns, and is moisture and lube free).

Benefits of Using the QB and Steam Regulator

There are many benefits to using a Proportion-Air steam regulator system – specifically a Proportion-Air 0 to 60 psig QB2/steam regulator assembly – especially when compared to the operation of traditional steam valves. This assembly was installed and subsequently performed extremely well.

Since the manufacturer did not require the ultra-high accuracy of the QB2, a QB1 was substituted. And regardless of whether the QB1 or QB2 was used, the control loop did not have to work as hard because the regulator could compensate for changes on its own without the assistance of sophisticated electronic controls.

Steam Control Issues
Steam Control Issues

Steam Cooking

QB I to P
Can use standard industrial air filtered 20 to 40 microns. They typically require a dry instrument air filtered to less than 5 microns.
Air can be saturated or dry with or without lube mist.
Steam Regulator Steam Valve
Diaphragm has a direct connection to downstream saturated steam pressure so it can automatically compensate for changes in pressure downstream due to changes in flow. Has no direct connection to pressure downstream and cannot connect for downstream changes without a PID loop closing the loop around pressure (or temperature).
Temperature is more accurate. Temperature is less accurate, because PID must always compensate for slight changes in pressure downstream.

What’s a Steam Regulator?

What's a Steam Regulator? And why it may be a much better choice than a complicated control valve My training ...
Read More
REQUEST QUOTE

Only looking for a replacement product? Please use this form

Most quotes within 6 hours of understanding your needs

Solving Steam Control Issues & Offering Alternatives ultima modifica: 2017-12-12T15:30:44-04:00 da Proportion-Air

Subscribe To Our Newsletter

Join our mailing list to receive the latest news and updates from our team.

You have Successfully Subscribed!